Prefessional Line

Overcurrent protection, motor and generator protection, high level differential protection

obr

Here you will find both individual and combinable digital relays with all protection functions for low and medium voltage applications.

AC and DC power range widths make PROFESSIONAL LINE transmissions as versatile as possible.

Connections to SCADA systems are achieved through standardized interfaces.

Overcurrent protection

ANSI

Device XI1-I XI1-E XI1-S XI1-E-R XI1-S-R XRI1-I-R XRI1-I-E XRI1-E-R
Documentation Manual Manual Manual Manual Manual Manual Manual Manual
Line PL PL PL PL PL PL PL PL
Current Transformer Inputs (MTP) 3 1 1 1 1 3 4 1
Voltage Transformer Inputs (MTN) 1 1 3 3
Binary inputs 2 2 2
Relay Output 2 2 2 2 2 4 4 4
Watchdog relay 1 1 1
50/51 Overcurrent time protection Yes Yes Yes
67 Control overcurrent protection time Yes
50N/51N Earth protection Yes Yes Yes Yes
50N/51N Earth resistance / Direct grounding Yes Yes
67N Ground direction protection Yes Yes Yes
50BF Electrical safety circuit breaker Yes Yes
Reset / Block Yes Yes Yes
Parameters 1 1 1
Error messages Yes Yes Yes
RS485 Open Data Protocol Optional Optional Optional Optional Optional Yes Yes Yes

 

ANSI

Device XN2-1 XN2-2 XRN2-1 XRN2-2 XRW1-4 XUF2 XUA1 XU2-AC XU1-DC XU1-E XF2 XG2
Documentation Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual
Line PL PL PL PL PL PL PL PL PL PL PL PL
Voltage Transformer Inputs (MTN) 3 3 3 3 3 3 3 3 1 3 3
Binary inputs 2 2 2
Relay Output 2 2 4 4 4 2 2 2 2 2 2 2
Watchdog relay 1 1 1
27/59 Voltage protection Yes Yes Yes Yes Yes Yes Yes Yes Yes
59N Residual stress Yes
47 Phase symmetry Yes
81O/U Frequency protection Yes Yes Yes Yes Yes Yes Yes
81 Frequency protection Yes Yes Yes
78 Vector shift Yes Yes Yes
Reset / Block Yes Yes Yes
Voltage dependent function Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Time data Yes Yes Yes
Parameters 1 1 1
Error messages Yes Yes Yes
Matrix relay output
RS485 Open Data Protocol Optional Optional Yes Yes Yes Optional Optional Optional Optional Optional Optional Optional

 

ANSI

Device XP2-R XS2 XE2 XR1
Documentation Manual Manual Manual Manual
Line PL PL PL PL
Current Transformer Inputs (MTP) 1 3
Voltage Transformer Inputs (MTN) 1
Relay Output 2 2 2 2
50/51 Overcurrent time protection Yes
32/37 Directional power Yes
64N Rotor earth protection Yes
40/76 Excited current protection Yes
Fault diode Yes
46 Negative sequential protection Yes
40 Running missing protection Yes
RS485 Open Data Protocol Optional Optional Optional Optional

 

ANSI

Device XD1-T XD1-G XD1-L
Documentation Manual Manual  Manual
Line PL PL PL
Current Transformer Inputs (MTP) 6 6 2
Relay Output 2 2 3
87T Differential protection: Transformer Yes
87G Differential protection: Generator Yes
87L Differential protection : Leadership Yes

 

ANSI

Device XM1
Documentation Manual
Line PL
Current Transformer Inputs (MTP) 3
Relay Output 2
Watchdog relay 1
50/51 Overcurrent time protection Yes
50N/51N Earth protection Yes
46 Negative securing protection Yes
51 Motor protection: Blocked rotor Yes
37 Motor Protection: Undercurrent Yes
49 Motor Protection: Thermal Protection Yes
RS485 Open Data Protocol Optional